Through our global network of testing experts and analytical equipment including chromatography (HPLC, GC, GC/MS) and atomic absorption spectroscopy (AAS, GFA, FIAS), Our goal is to provide test services as efficiently as possible to maximize our customers' profits. For more information about our services, contact one of our experts today.
Note: this service is for Research Use Only and Not intended for clinical use.

Refrigerant Compatibility and Mechanical Performance Evaluation of O-Rings for HVAC Applications
A global HVAC component manufacturer engaged our laboratory to evaluate the mechanical performance and refrigerant compatibility of elastomeric O-rings used in refrigeration and air-conditioning systems. Furthermore, as modern HVAC systems transition toward lower-global-warming-potential (GWP) refrigerants, sealing materials must maintain sufficient strength, elasticity, dimensional stability, and resistance to chemical exposure under elevated temperatures.
The client submitted two types of O-rings (green O-ring and black O-ring) for comprehensive evaluation, including hardness, tensile properties, heat aging resistance, and fluid immersion performance in multiple HVAC refrigerants. The objective was to compare material behavior and assess suitability for long-term sealing applications under demanding operating environments.
Our laboratory performed a multi-stage evaluation program following internationally recognized ASTM standards to characterize both baseline mechanical properties and environmental durability.
The testing program included:
| Evaluation Category | Test Method | Test Conditions |
| Hardness, Tensile Strength & Elongation | ASTM D 1414 / ASTM D 412 Method B / ASTM D 1415 | Tensile testing at 20 in/min; IRHD hardness measured at 30 seconds |
| Heat Aging Resistance | ASTM D 1414 / ASTM D 573 | 70 hours aging at 302 °F (150 °C) in forced-air oven |
| Refrigerant Immersion Compatibility | ASTM D 1414 / ASTM D 471 | 70 hours immersion at 302 °F (150 °C) in R32, R1234yf, R1234ze, and R410a refrigerants |
The evaluation focused on key performance indicators including hardness change, tensile strength retention, elongation retention, and volume change after thermal and chemical exposure.
The testing program evaluated the O-rings' mechanical properties, thermal aging resistance, and compatibility with different HVAC refrigerants. The results demonstrated that the two elastomer formulations exhibited different performance characteristics under mechanical loading and environmental exposure conditions. The details are as follows.
Initial Mechanical Properties
| Test Parameter | Green O-Ring | Black O-Ring |
| Microhardness (IRHD) | 67 | 64 |
| Tensile Strength | 2,520 psi | 3,150 psi |
| Ultimate Elongation | 350% | 255% |
| 100% Modulus | 495 psi | 510 psi |
| 200% Modulus | 1,460 psi | 2,180 psi |
| 300% Modulus | 2,180 psi | — |
Initial mechanical testing confirmed that both O-ring materials exhibited suitable elastomeric properties for HVAC sealing applications. The green O-ring demonstrated higher flexibility and elongation capability, while the black O-ring showed higher tensile strength and modulus values, indicating greater stiffness and load resistance.
Heat Aging Resistance
| Test Parameter | Green O-Ring | Black O-Ring |
| Hardness Change | +6 points | +5 points |
| Tensile Strength Change | +14% | -1% |
| Elongation Change | -20% | -12% |
| Surface Condition | Normal | Normal |
Both O-ring materials maintained normal surface conditions after thermal aging. The green O-ring showed slightly improved tensile strength after aging, while the black O-ring exhibited minimal tensile change. The moderate reduction in elongation observed for both materials reflected typical thermal aging effects without significant structural deterioration.
Refrigerant Immersion Performance
| Refrigerant | Test Parameter | Green O-Ring | Black O-Ring |
| R32 | Hardness Change | -15 points | -3 points |
| Tensile Strength Change | -22% | -38% | |
| Elongation Change | -23% | -15% | |
| Volume Change | +26% | +11% | |
| R1234yf | Hardness Change | -3 points | +12 points |
| Tensile Strength Change | -8% | -61% | |
| Elongation Change | -26% | -62% | |
| Volume Change | +5% | +9% | |
| R1234ze | Hardness Change | -6 points | -2 points |
| Tensile Strength Change | -13% | -23% | |
| Elongation Change | -28% | -19% | |
| Volume Change | +4% | +1% | |
| R410a | Hardness Change | +1 point | +3 points |
| Tensile Strength Change | +2% | -5% | |
| Elongation Change | -15% | +3% | |
| Volume Change | +1% | +1% |
Refrigerant immersion results demonstrated that elastomer compatibility was highly dependent on refrigerant chemistry. Both O-ring materials showed the most stable performance under R410a exposure, with minimal volume expansion and limited mechanical property changes. Under R32 exposure, both materials experienced noticeable swelling, although the green O-ring maintained better tensile retention. R1234yf exposure produced the most significant difference between the two materials, with the green O-ring maintaining substantially better tensile and elongation retention compared with the black O-ring. These results highlight the importance of refrigerant-specific elastomer selection for reliable HVAC sealing performance.
Through standardized ASTM-based mechanical and chemical resistance testing, our laboratory provided the client with reliable performance data to support O-ring material selection and HVAC component qualification. Moreover, the comprehensive evaluation enabled the client to:
Reliable sealing performance is essential for maintaining HVAC system efficiency, safety, and service life. Our laboratory provides comprehensive elastomer and polymer testing solutions, including mechanical characterization, thermal aging evaluation, chemical resistance testing, and refrigerant compatibility assessments.
👉 Partner with our technical experts to verify your sealing materials and accelerate product qualification for demanding industrial applications.
Do not know how to place an order, please refer to the flow chart shown below.
Submit quotation request |
A technical manager will contact you within 24 hours |
You will review and approve the final price and place an order |
Confirm with you and make the payment |
Instruct you to ship your samples and form |
Analytic report delivery |